Mauritius Explosion-proof single-acting intelligent valve positioner
Category:
MauritiusControl Strategy of Membrane Control Valve
MauritiusBall valve control strategy
MauritiusButterfly valve control strategy
MauritiusDiaphragm valve control strategy
MauritiusControl Strategy of Damper Valve
Product Description

The TORLEO single-acting smart valve positioner uses nozzle-flapper technology and is compatible with pneumatic control valves with single-acting cylinders (such as diaphragm control valves, single-acting ball valves, single-acting butterfly valves, etc.). It is widely used for precise control of flow rate and other parameters in the production processes of various industries, including petroleum, chemical, metallurgical, power, and papermaking.

The technical principle of the TORLEO smart valve positioner is to use an electrical balance (digital balance) principle instead of the traditional force balance principle. It converts the electrical control command into a pneumatic positioning increment to achieve valve position control; it uses digital on/off signals to drive the pneumatic actuator; the valve position feedback signal is directly transmitted through a high-precision position sensor, realizing an electrical/pneumatic conversion function. The microprocessor in the smart valve positioner receives a 4-20mA setpoint signal and compares it with the actual valve position value fed back by the valve position sensor. If a deviation is detected, it immediately outputs an electrical control command (PWM digital method) to the nozzle flapper's I/P control unit based on the magnitude and direction of the deviation, thereby adjusting the air flow rate entering the actuator's air chamber, which means the control valve converts the control command into a pneumatic displacement increment. When the deviation between the actual valve position and the setpoint is large (high-speed zone), the positioner outputs a continuous signal; if the deviation is not large (low-speed zone), the positioner will output a pulse signal; when the deviation is very small (adaptive or adjustable dead zone state), there is no positioner output. At this time, the actual valve position reaches the setpoint, and the mechanism reaches a balanced state, that is, a certain set current corresponds to a certain valve position.


| Serial Number |
Performance Indicators |
TORLEO (China) |
ABB (Switzerland) |
SAMSON (Germany) |
Azbil (Japan) |
Comparative Remarks |
| 1 |
Pneumatic Component Characteristics |
Digital I/P Converter Pneumatic 3/3 Slide Valve |
Analog I/P Converter Pneumatic 3/3 Slide Valve |
I/P Converter Pneumatic Amplifier |
I/P Converter Pneumatic Amplifier |
Superior to imports |
| 2 |
I/P Drive Method |
Digital (PWM) |
Analog (Voltage) |
Analog (Voltage) |
Analog (Voltage) |
Superior to imports |
| 3 |
I/P Power Consumption |
0.8mw |
1.6mw |
5mw |
18mw |
Superior to imports |
| 4 |
Vibration Resistance Index |
20g |
20g |
10g |
10g |
Meets import standards |
| 5 |
Fault Lockout |
Yes (built-in function) |
Yes (built-in function) |
Requires external accessories |
Requires external accessories |
Meets import standards |
| 6 |
Temperature Drift Compensation |
With compensation technology |
With compensation technology |
With compensation technology |
Without compensation technology |
Meets import standards |
| 7 |
Air Source Pressure |
1.4-6bar |
1.4-6bar |
1.4-6bar |
1.4-7bar |
Meets import standards |
| 8 |
Air Quality |
ISO8573-1 particulate matter class 3, Oil content less than 1mg/m3, Dew point less than 10k |
ISO8573-1 particulate matter class 3, Oil content less than 1mg/m3, Dew point less than 10k |
ISO8573-1 particulate matter class 4, Oil content 3g, dew point 3g |
ISO8573-1 particulate matter class 4, Oil content 3g, dew point 3g |
Meets import standards |
| 9 |
Steady-state air consumption |
0.056Nm3/h Independent of air pressure |
0.085Nm3/h Independent of air pressure |
0.11Nm3/h Independent of air pressure |
0.24Nm3/h(1.4bar) 0.3Nm3/h(5bar) |
Superior to imports |
| 10 |
Control Precision |
0.1%-0.3% |
0.1%-0.3% |
0.3%-0.5% |
0.5%-1.0% |
Meets import standards |
| 11 |
Auto-tuning |
One-button foolproof setting 2-3 minutes |
Multi-step menu setting 3-5 minutes |
Multi-step menu setting 3-5 minutes |
Toggle switch setting 8-15 minutes |
Superior to imports |
| 12 |
Minimum operating current |
3.4mA |
3.4mA |
3.5mA |
3.8mA |
Meets import standards |
| 13 |
Explosion-proof standard |
Exia IIC T6 |
Exia IIC T6 |
Exia IIC T6 |
Exia IIC T6 |
Meets import standards |
| 14 |
Explosion-proof standard |
Exd IIC T6 |
Exd IIC T6 |
Exd IIC T6 |
Exd IIC T6 |
Meets import standards |
| 15 |
Backup function |
Yes |
No |
No |
No |
Superior to imports |
| 16 |
Price |
Moderate |
High |
High |
High |
High cost performance |

| Serial Number |
Project |
TOP-5879F |
TOP-7743F |
| 1 |
Input signal |
4-20mA |
|
| 2 |
Input pressure |
1.4-6kgf/cm²(0.14-0.6Mpa) |
|
| 3 |
Stroke |
10-150mm or 0-120º |
|
| 4 |
Impedance |
Max 460Ω/20mA(DC) |
|
| 5 |
Air source interface |
PT (NPT) 1/4 |
|
| 6 |
Pressure gauge interface |
PT (NPT) 1/8 |
|
| 7 |
Power interface |
PF 1/2 (G 1/2) |
|
| 8 |
Repeatability |
±0.2%F.S. |
|
| 9 |
Operating temperature |
-30℃∽85℃ |
|
| 10 |
Explosion-proof temperature |
-40℃∽40℃ |
|
| 11 |
Linearity |
±0.3%F.S. |
|
| 12 |
Hysteresis |
±0.2%F.S. |
|
| 13 |
Sensitivity |
±0.2%F.S. |
|
| 14 |
Air consumption |
Less than 0.03kg/h (irrespective of air source pressure) |
|
| 15 |
Output characteristics |
Linear, quick-opening, equal percentage, user-defined |
|
| 16 |
Auto-tuning method |
One-button auto-tuning |
|
| 17 |
Material grade |
Die-cast aluminum |
Stainless steel 316 |
| 18 |
Explosion-proof grade |
Exia IIC T4-T6 |
|
| 19 |
Explosion-proof grade |
Exd IIC T4-T6 |
|
| 20 |
Weight |
2kg |
3.6kg |



ØExternal dimensions
Top view

Bottom view

Figure 2 Positioner external installation dimensions
ØActuator introduction

Figure 3 Pneumatic Diaphragm Control Valve Actuator
ØInstallation component introduction

Figure 4 Positioner installation components
| Give16mAInstruction, setMAN-SENSMode |
↓
| Air Source: Adjust the air source to the required pressure (e.g., 0.4 MPa), and check the airtightness of the fitting |
↓
| Set Actuator Type: Set P1-1 to LINE, and select YES in P1_6SAVE to save. |
↓
| Move the valve up and down to see if the angle between the lever and the horizontal is within-30degrees to+30degrees or so |
↓
| Check if the valve is stuck: In MAN-SENS mode, press and hold the increase or decrease key to see if the valve runs smoothly |
↓
| Set Valve Upper and Lower Limits: This valve only needs to set the upper limit value in P3_2 |
↓
| One-button Auto-tuning: In AUTO_RDT, press and hold the increase key for 5 seconds until the countdown ends, then release the key to Enter auto-tuning. After auto-tuning is complete, it will automatically Enter AUTO_RDT operation. The tuning time is about 2-3 minutes. |
↓
| Check if the valve position and instruction are consistent: If opposite, change the value of P2_4 and save. |
↓
| Check if the display and position are consistent: If opposite, change the value of P4_3 and save. |
↓
| Check if the feedback current and valve position are consistent. If opposite, change the value of P7_3 and save. |
↓
| Check the control effect |
↓
| End |
| Serial Number |
Problem |
Solution |
| 1 |
Current is given, but the LCD screen is not lit |
1) Check if the instruction line is connected in reverse 2) Check if the current reaches the terminals of the board 3) Unplug the plug connected to the main board. If it is still not lit, the main board is faulty. If it recovers, the unplugged component is faulty. |
| 2 |
There is an air leak sound outside the positioner after air is passed through |
1) Check the fitting 2) Check the air tube 3) Check the actuator |
| 3 |
There is a significant air leak sound inside the positioner after air is passed through |
1) Check between the pressure gauge block and the positioner body. If so, tighten it. If it still leaks, reinstall the gasket. 2) Check if the fixing screws of the IP are tightened, and check the gasket under the IP. 3) The IP may be leaking. |
| 4 |
Exhaust is always accompanied when the actuator is inflated |
1) It is recommended to replaceIP |
| 5 |
After air is passed through, inflation is always given without instructionsOUT1Inflation |
1) Repeatedly press and hold the increase and decrease keys in manual mode 2) Change IP |
| 6 |
The valve does not move and the pressure does not increase in manual mode |
1) Check for external air leaks 2) Try restoring factory settings 3) Change the positioner |
| 7 |
The displayed position does not change when the manual valve moves |
1) Check if the feedback rod moves accordingly 2) Check if the potentiometer plug is properly inserted 3) Check if the potentiometer rotates with the gear |
| 8 |
CALC_ERR |
1) Check if the valve is stuck 2) Check if the feedback rod moves accordingly |
| 9 |
ZERO_ERR |
1) Determine the zero position of the positioner. At this time, is the horizontal deviation of the feedback rod too large? |
| 10 |
NO_SCALL |
1) Check if the upward and downward times are sufficient 2) Check if the feedback rod is loose |
| 11 |
Tuning inSD6Does not move |
1) Check if the installation is reasonable 2) Check if the feedback rod angle is less than 60°. If it is less than 60°, increase it. 3) Retune |
| 12 |
Poor control effect |
First determine whether the upward control is poor or the downward control is poor, and modify the corresponding parameters to improve it. Generally, inflation corresponds to P5_1, P5_3, and P5_5 exhaust corresponds to P5_2, P5_4, P5_6 1) Overshoot: If it is inflation overshoot, first reduce P5_1. If it cannot be satisfied, reduce P5_3 appropriately. Otherwise, modify the other set of corresponding parameters. Modify about 50 each time. 2) Undershoot: If it is inflation undershoot, increase P5_3 appropriately. Otherwise, modify the other set of corresponding parameters. 3) Small amplitude oscillation: Reduce P5_5 and P5_6 by one-third each. If it doesn't work, reduce P5_3 and P5_4 4) If the problem persists, try readjusting. |
| 13 |
Control Deviation |
1) Check the instruction display accuracy; if the deviation is large, EnterP8the menu to recalibrate. |