Iran Split remote transmission intelligent valve positioner
Category:
IranControl Strategy of Membrane Control Valve
IranBall valve control strategy
IranButterfly valve control strategy
IranDiaphragm valve control strategy
IranControl Strategy of Damper Valve
Product Description

The TORLEO tubeless smart valve positioner is used with pneumatic control valves (such as diaphragm control valves, ball valves, butterfly valves, etc.), and is widely used in the precise control of flow rate in the production processes of industries such as petroleum, chemical engineering, metallurgy, power, and papermaking.

The technical principle of the TORLEO intelligent valve positioner is to use an electrical balance (digital balance) principle to replace the traditional force balance principle, converting the electrical control command into a pneumatic positioning increment to achieve valve position control; using digital on/off signals to drive the pneumatic actuator; the valve position feedback signal is directly transmitted through a high-precision position sensor, realizing the electro-pneumatic conversion function. The microprocessor in the intelligent valve positioner receives a 4-20mA setpoint signal and compares it with the actual valve position value fed back by the valve position sensor. If a deviation is detected, it immediately outputs an electrical control command (PWM digital method) to the nozzle flapper I/P control unit according to the magnitude and direction of the deviation, thereby adjusting the airflow entering the actuator air chamber, that is, the control valve converts the control command into pneumatic displacement increment. When the deviation between the actual valve position and the setpoint is large (high-speed zone), the positioner outputs a continuous signal; if the deviation is not large (low-speed zone), the positioner will output a pulse signal; when the deviation is very small (adaptive or adjustable dead zone state), there is no positioner output, at this time, the actual valve position reaches the setpoint, and the mechanism reaches a balanced state, that is, a certain set current corresponds to a certain valve position.

Figure 1 TORLEO intelligent valve positioner schematic diagram

| Serial Number |
Performance Indicators |
TORLEO (China) |
ABB (Switzerland) |
SAMSON (Germany) |
Azbil (Japan) |
Comparison Description |
| 1 |
Pneumatic component characteristics |
Digital I/P converter Pneumatic 3/3 slide valve |
Analog I/P converter Pneumatic 3/3 slide valve |
I/P converter Pneumatic amplifier |
I/P converter Pneumatic amplifier |
Superior to imported products |
| 2 |
I/P drive method |
Digital (PWM) |
Analog (voltage) |
Analog (voltage) |
Analog (voltage) |
Superior to imported products |
| 3 |
I/P power consumption |
0.8mw |
1.6mw |
5mw |
18mw |
Superior to imported products |
| 4 |
Vibration resistance index |
20g |
20g |
10g |
10g |
Reaches imported standards |
| 5 |
Fault interlock |
Yes (built-in function) |
Yes (built-in function) |
Requires external accessories |
Requires external accessories |
Reaches imported standards |
| 6 |
Temperature drift compensation |
With compensation technology |
With compensation technology |
With compensation technology |
Without compensation technology |
Reaches imported standards |
| 7 |
Air source pressure |
1.4-6bar |
1.4-6bar |
1.4-6bar |
1.4-7bar |
Reaches imported standards |
| 8 |
Air quality |
ISO8573-1 particulate matter class 3, Oil content less than 1mg/m3, Dew point less than 10k |
ISO8573-1 particulate matter class 3, Oil content less than 1mg/m3, Dew point less than 10k |
ISO8573-1 particulate matter class 4, Oil content 3g, dew point 3g |
ISO8573-1 particulate matter class 4, Oil content 3g, dew point 3g |
Reaches imported standards |
| 9 |
Steady-state air consumption |
0.056Nm3/h Irrelevant to air pressure |
0.085Nm3/h Irrelevant to air pressure |
0.11Nm3/h Irrelevant to air pressure |
0.24Nm3/h(1.4bar) 0.3Nm3/h(5bar) |
Superior to imported products |
| 10 |
Control Precision |
0.1%-0.3% |
0.1%-0.3% |
0.3%-0.5% |
0.5%-1.0% |
Reaches imported standards |
| 11 |
Self-tuning |
One-button foolproof setting 2-3 minutes |
Multi-step menu setting 3-5 minutes |
Multi-step menu setting 3-5 minutes |
Toggle switch setting 8-15 minutes |
Superior to imported products |
| 12 |
Minimum Operating Current |
3.4mA |
3.4mA |
3.5mA |
3.8mA |
Reaches imported standards |
| 13 |
Explosion-proof Standard |
Exia IIC T6 |
Exia IIC T6 |
Exia IIC T6 |
Exia IIC T6 |
Reaches imported standards |
| 14 |
Explosion-proof Standard |
Exd IIC T6 |
Exd IIC T6 |
Exd IIC T6 |
Exd IIC T6 |
Reaches imported standards |
| 15 |
Backup Function |
Yes |
No |
No |
No |
Superior to imported products |
| 16 |
Price |
Moderate |
High |
High |
High |
High Cost Performance |

| Serial Number |
Project |
Explosion-proof Type |
Explosion-proof Type |
| 1 |
Input Signal |
4-20mA, can be set as proportional control input The proportional range can be set between 20-100% |
|
| 2 |
Input Pressure |
1.4-6kgf/cm²(0.14-0.6Mpa) |
|
| 3 |
Stroke |
10-150mm or 0-120º |
|
| 4 |
Impedance |
Maximum 460Ω/20mA(DC) |
|
| 5 |
Air Source Interface |
PT (NPT) 1/4 |
|
| 6 |
Pressure Gauge Interface |
PT (NPT) 1/8 |
|
| 7 |
Power Interface |
PF 1/2 (G 1/2) |
|
| 8 |
Repeatability |
±0.2%F.S. |
|
| 9 |
Operating Temperature |
-30℃∽85℃ |
|
| 10 |
Explosion-proof Temperature |
-40℃∽40℃ |
|
| 11 |
Linearity |
±0.3%F.S. |
|
| 12 |
Hysteresis |
±0.2%F.S. |
|
| 13 |
Sensitivity |
±0.2%F.S. |
|
| 14 |
Air Consumption |
Less than 0.03kg/h (irrespective of air source pressure) |
|
| 15 |
Output Characteristics |
Linear, quick-opening, equal percentage, user-defined |
|
| 16 |
Self-tuning Method |
One-button self-tuning |
|
| 17 |
Material Grade |
Die-cast Aluminum |
Stainless Steel 316 |
| 18 |
Explosion-proof Grade |
Exia IIC T4-T6 |
|
| 19 |
Explosion-proof Grade |
Exd IIC T4-T6 |
|
| 20 |
Weight |
2kg |
3.6kg |



ØAppearance Dimensions
Plan View

Elevation View

Figure 2 Positioner External Installation Dimensions Diagram
ØActuator Introduction

Figure 3 Pneumatic Diaphragm Control Valve Actuator
ØInstallation Component Introduction

Figure 4 Components for Positioner Installation
| Give16mAinstructions, setMAN-SENSmode |
↓
| Air source: Adjust the air source to the required pressure (e.g., 0.4 MPa), and check the airtightness of the fitting |
↓
| Set actuator type: Set P1-1 to LINE, and select YES in P1_6SAVE to save |
↓
| Move the valve up and down to see if the angle between the lever and the horizontal is within-30degrees to+30degrees |
↓
| Check if the valve is stuck: In MAN-SENS mode, long-press the increase or decrease button to see if the valve runs smoothly |
↓
| Set the upper and lower limits of the valve: This valve only needs to set the upper limit value in P3_2 |
↓
| One-button auto-tuning: In AUTO_RDT, long-press the increase button for 5 seconds until the countdown ends, then release the button to Enter auto-tuning. After auto-tuning is complete, it will automatically Enter AUTO_RDT operation. The tuning time is about 2-3 minutes |
↓
| Check if the valve position and instruction are consistent: If they are opposite, change the value of P2_4 and save |
↓
| Check if the display and position are consistent: If they are opposite, change the value of P4_3 and save |
↓
| Check if the feedback current and valve position are consistent. If they are opposite, change the value of P7_3 and save |
↓
| Check the control effect |
↓
| End |
| Serial Number |
Problem |
Solution |
| 1 |
The LCD screen does not light up when current is applied |
1) Check if the command line is reversed 2) Check if the current reaches the terminals of the board 3) Unplug the plug connected to the main board. If it still does not light up, the main board is faulty; if it recovers, the unplugged component is faulty |
| 2 |
There is an air leak sound outside the positioner after air is applied |
1) Check the fitting 2) Check the air tube 3) Check the actuator |
| 3 |
There is a significant air leak sound inside the positioner after air is applied |
1) Check between the pressure gauge block and the positioner body. If so, tighten it. If it still leaks, reinstall the gasket 2) Check if the fixing screws of the IP are tightened, and check the gasket under the IP 3) The IP may be leaking |
| 4 |
Exhaust is always present when the actuator is inflated |
1) It is recommended to replaceIP |
| 5 |
Inflation is always applied after air is applied, but no instructions are givenOUT1Inflation |
1) Manually press and hold the increase and decrease buttons repeatedly in manual mode 2) Replace IP |
| 6 |
The valve does not move and the pressure does not increase in manual mode |
1) Check for external air leaks 2) Try restoring factory settings 3) Replace the positioner |
| 7 |
The display position does not change when the manual valve moves |
1) Check if the feedback rod is moving 2) Check if the potentiometer plug is inserted correctly 3) Check if the potentiometer rotates with the gear |
| 8 |
CALC_ERR |
1) Check if the valve is stuck 2) Check if the feedback rod is moving |
| 9 |
ZERO_ERR |
1) Determine the zero position of the positioner. At this time, is the horizontal deviation of the feedback rod too large? |
| 10 |
NO_SCALL |
1) Check if the up and down times are sufficient 2) Check if the feedback rod is loose |
| 11 |
Tuning inSD6does not move |
1) Check if the installation is reasonable 2) Check if the feedback rod angle is less than 60°. If it is less than 60°, increase it 3) Retune |
| 12 |
Poor control effect |
First determine whether the upward control is poor or the downward control is poor, and modify the corresponding parameters to improve it. Generally, inflation corresponds to P5_1, P5_3, and P5_5, and exhaust corresponds to P5_2, P5_4, and P5_6 1) Overshoot: If it is inflation overshoot, first reduce P5_1, if it cannot be satisfied, then appropriately reduce P5_3, otherwise modify the other corresponding parameter group, modify about 50 each time 2) Undershoot: If it is inflation undershoot, then appropriately increase P5_3, otherwise modify the other corresponding parameter group 3) Small amplitude oscillation: Reduce P5_5 and P5_6 by one third each, if it doesn't work, reduce P5_3 and P5_4 4) If it still cannot be solved, try readjusting it |
| 13 |
Control Deviation |
1) Check the instruction display accuracy; if the deviation is large, EnterP8Menu Recalibration |